Capteur NDIR à diffusion à sortie analogique et numérique

Manufacturer
Smartgas
HTTS ref.
HTS-OPT-0014
HTDS ref.
CAPTEUR NDIR A DIFFUSION A SORTIE ANALOGIQUE ET NU
Capteur NDIR à diffusion à sortie analogique et numérique

Description

CONNECT smartMODUL // Technical Data Infrared gas sensor for diffusion with analogue and digital interfaces Infrared gas sensor using dual beam technology, with measurement and reference channel, for monitoring room air and process control applications

Key features

  • Grande Précision
  • Excellente sélectivité
  • Durée de vie > 10 ans

Technical specifications

Accuracy
≤ ±2 % FS 1
Humidity
0 % to 95 % rel. humidity (not condensing)
Telephone
+49 (0) 7131/797553-0 | Telefax: +49 (0) 7131/797553-10 | www.smartgas.eu | [email protected]
0-2000 ppm
C1-030205-00000
Dimensions
72 mm x 55 mm x 34 mm (L x W x H)
Gas supply
by diffusion
Resolution
1 ppm to 0.01 Vol.% FS 1
ammonia NH
0-3.5 Vol.-% C1-200356-00000
smartMODUL
// Technical Data
0-20 Vol.-%
C1-212207-00000
Calibration
zero by jumper / SW and span by jumper
methane CH4
0-4.4 Vol.-% (0-100 % LEL) C1-040446-00000
Air pressure
950 to 1050 mbar
Maximum load
125 Ω
Warm-up time
< 2 minutes (start up time)
propane C3H8
0-1.7 Vol.-% (0-100 % LEL) C1-050176-00000
Repeatability
≤ ±2 % FS 1
ethylene C2H4
0-2.4 Vol.-% (0-100 % LEL) C1-030246-00000
Supply current
70 mA average, max. 140 mA
Supply voltage
12 - 28 V DC ± 5 %
n-butane C4H10
0-1.4 Vol.-% (0-100 % LEL) C1-020146-00000
Linearity error
≤ ±1 % FS 1
Measurement range
dependent on model – see list
Power consumption
< 1 Watt
refrigerant R404a
0-2000 ppm C1-740205-00000
carbon monoxide CO
0-2 Vol.-% C1-221206-00000
Response time (t90)
Appr. 30 s
Storage temperature
-20 °C to 60 °C
Digital output signal
Modbus ASCII via RS485
Lower detection limit
≤ 1 % FS 1 (typically)
Measurement principle
Non Dispersive Infra-Red (NDIR), dual wavelength
Operating temperature
-10 °C to 40 °C
Analogue output signal
0 - 20 mA linear
pentafluoroethane R125
0-2000 ppm C1-720205-00000
Temp. dependence (span)
≤ ±0.2 % FS 1 per °C
Temp. dependence (zero)
≤ ±0.01 % FS 1 per °C
tetrafluoroethane R134a
0-2000 ppm C1-710205-00000
sulphur hexafluoride SF6
0-1000 ppm (0-100 % TLV) C1-600105-00000
• Dual beam technology
acetylene C2H2 0-2.3 Vol.-% (0-100 % LEL) C1-010236-00000
chlorodifluoromethane R22
0-2000 ppm C1-700205-00000
Long term stability (span)
≤ ±2 % FS 1 over 12 month period
Long term stability (zero)
≤ ±2 % FS 1 over 12 month period
Pressure dependence (span)
0.1 % to 0.2 % per mbar 2
Pressure dependence (zero)
-
• Gas entry by diffusion
0-5 Vol.-% C1-212506-00000
dichlorotrifluoroethane R123
0-2000 ppm C1-730205-00000
• Infrared measuring principle (NDIR)
Gases * Measurement range Model type
• Zero and span calibration by jumper
carbon dioxide CO 0-5000 ppm (0-100 % TLV) C1-212505-00000
• Analogue interfaces (e.g. 4 – 20 mA)
3
* More gases and measuring ranges on request
Sensors similar to the illustration

HTTSystems product sheet

Download the datasheet in our colours and contact details, or read it full screen.

Request a quote

Reference HTS-OPT-0014 is carried into your file. You fill in the context, an engineer takes it from there.

Request a quote

Talk to an engineer

A question about installation, consumables or compatibility before pricing? Our engineers answer from Douala.

Ask the question

Close to this one

Same family, or same division when the family is thin.

WhatsApp, pre-filled conversation with Hello HTTSystems, I am writing from your website.